Technical specifications

General

Address:Willem Fenengastraat 16
City:Amsterdam
No. of floors:10, including 1 basement
Total floor area:19,833 m2
Lettable floor area:13,222 m2

Sustainability

Energy label:A+++
Energy index:BENG
BREEAM:“Green” Design certificate very good
WELL:Ambition Gold
Energy type:Green energy (heat storage). No natural gas.
Solar energy:180 panels

Outdoor areas

Continuous wrap around terrace
area on each floor:
1,938 m2
Roof garden (second floor):1,229 m2
Waterfront terrace (ground floor):200 m2
West side terrace (ground floor):333 m2
Potential city-facing roof terrace:
(8st verdieping)
135 m2

Parking

No. of car parking spaces:140
(spread across underground, ground floor and
upper floor areas)
Type of parking:Indoor
No. of bike parking spaces:425 spaces
Incl. electric chargers for cars.

Access and security

Electronic access system, intercom system,
anti-break-in system, CCTV system.

Vertical transport

Elevators:4 (capacity per elevator: 1,850 kg, 18 persons)
Stairwells:4 stuks

Structural specifications

Ceiling height (ground floor):approx. 7,000 mm
Ceiling height (office floors):2,900 mm
Facade modular sections (per section):5,400 mm
Division options (per section):1,800 mm
Doors to balconies:1 for every 5,400 mm
Floor load (offices):4,0 kN/m²
Occupancy category:10 m² per person

Sanitary facilities

Toilets:Each floor has 4 toilet rooms for shared use.
Showers:Shower facilities are available in the basement near the bike shed.

External wall finishes

Wall finish type:Aluminium elements,
Petrarca reconstituted stone panels and
aluminium window frames.
Percentage of window area:Ground floor
approx. 84%, upper floors approx. 48%.
Open windows:1 open window/door for
every 5,400 mm.
Balconies:Concrete floors and wooden ceilings.
External blinds:Installed on south facade.

Internal wall finishes

Walls:the core, entrance and corridor walls
have a smooth stucco finish and are painted
(RAL 9016). The external walls in the leased
area have a concrete finish.

Flooring

The entrance and corridor floors are finished with Marazzi floor tiles. The leased areas on the ground floor come with screed.
The leased areas on the first floor and above
have a raised floor.

Partition walls

Tenants can install partition walls within the
leased area at their own expense and risk. The lessor has drawn up installation equirements
for these, in particular with regard to mounting
on the aluminium window frames.

Electrical system

Length of electricity meters: 1 intermediate
metre per floor.
Type of cable ducts: To be installed in raised
floor at tenant’s expense; no cable ducts
under the raised floor.
Type of electrical sockets: To be installed in a raised floor at tenant’s expense. Facilities under the floor ready for connection.

Lighting

Type of lighting:LED
Lighting level in office area:500 lux
Lighting level in corridors/entrance hall:200 lux
Motion detectors
Daylight-dependent operation

Fire safety

Offices:Type A non-automatic fire detection
and evacuation system.
Car park:Type B automatic fire detection and evacuation system.

Ventilation

Type of ventilation:Constant flow, supplied
through concealed grid in climate ceilings.
Compartmentalisation options:Every 3,600 mm
(every 5,400 mm in some parts).
Fresh air volume:60 m³ per hour per office space (1 person/10 m²).

Cooling

Type of cooling:Climate ceiling with low-temperature heating/high-temperature cold water
pipes and underfloor heating/cooling in the
entrance hall. Energy-efficient high-temperature
cooling/low-temperature heating via CHP system.
Type of control:Climate can be controlled using
the control panel on each floor or a smartphone app.
Partitioning options:Every 3,600 mm (every
5,400 mm in some parts), with system adjustments.
Systems can be adapted at tenant’s
expense.
Type of generation:2x mono long-term
energy storage sources (hot and cold) in the
ground (capacity 40 m³/h per well). Combined
with 2 heat pumps of 200 kW each. A further
2 heat pumps of 110 kW each are installed on
the roof to cover peak demand. Supplemented
by 2 electric boilers of 80 kW. Cooling capacity
internally 35 W/m² (7 W/m² lighting, 8 W/m²
people, 20 W/m² equipment).

Heating

Type of heating:Climate ceiling with cooled water pipes and underfloor heating/cooling
in the entrance hall. Energy-efficient lowtemperature
heating.
Type of control:Climate can be controlled using the control panel on each floor or a smartphone app.
Partitioning options:Every 3,600 mm
(every 5,400 mm in some parts), with system adjustments. Systems can be adapted at tenant’s expense.
Type of generation:2x mono long-term energy storage sources (hot and cold) in the ground (capacity 40 m³/h per well). Combined with 2 heat pumps of 200 kW each. A further 2 heat pumps of 110 kW each are installed on the roof to cover peak demand. Supplemented by 2 electric boilers of 80 kW.

Raised floor

Height under floor:112 mm
Finish in carpet or PVC tile.
Specified height of floor finish:15 mm
Floor screed installation:Floor screed must be installed such that it can be removed without damaging computer floor tiles.
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.